NFPA 70B

NFPA 70B is now a standard. Find the heat before it finds you.

GEM helps New Jersey plants meet NFPA 70B with infrared surveys, arc flash studies and labeling, and preventive maintenance on switchgear, panels and transformers, all scheduled around production.

Sound familiar?

  • NFPA 70B changed from a recommended practice to a standard (2023 edition), and you don’t have a documented maintenance program. Insurers and auditors are starting to ask for one.
  • Your arc-flash labels are missing, outdated, or don’t match the gear. Every change since the last study makes them less accurate.
  • You can’t open gear without shutting down production. So maintenance keeps getting pushed back.
  • Hidden problems don’t announce themselves. Loose terminations, shared neutrals and overfilled conduit run hot for years until something fails.

How GEM solves it

GEM delivers complete NFPA 70B programs: infrared surveys by certified thermographers, arc flash studies stamped by a licensed New Jersey Professional Engineer, and the corrective work, all under one contract and one point of contact.

  • Infrared surveys: Performed by Infraspection Institute Certified Infrared Thermographers, following the Infraspection Institute’s Standard for Infrared Inspection of Electrical Systems & Rotating Equipment. Our crews open and prep the gear (about 50 pieces of equipment in one morning on a recent plant survey), then correct what the scan finds.
  • Arc flash: Arc flash studies stamped by a licensed New Jersey Professional Engineer, plus labeling and label updates after changes to the gear.
  • Preventive maintenance: Torque checks, cleaning, panel and transformer replacements, and corrective work on IR findings.
  • Scheduled around production: Night and weekend work is planned, and after-hours backup is available if something can’t wait.
Switchgear section opened for inspection, showing bus and fuses

Proof: a burned-up UPS, a shared neutral, and a conduit running hot

When a UPS burned up at a client’s new facility, we tested the IT room and found the real cause. When power was relocated at some point, two circuits had been left sharing one neutral. That neutral overloaded and burned up. We also found the main 3/4″ conduit to the ladder tray severely overloaded and running extremely hot. Both problems were invisible until the failure, and both are exactly what an NFPA 70B infrared survey is designed to catch.

Example from a recent infrared survey

On a recent infrared survey of an operating facility, a Level III certified thermographer scanned the building’s switchboards, panelboards, safety switches and dry-type transformers under normal load. Most of the equipment checked out. A handful of items did not, and the most serious were rated Priority 1. Here are three of them, in plain language.

1. A dry-type transformer overheating on one phase

Infrared image of a dry-type transformer with one phase winding much hotter than the other two
Photo of the same dry-type transformer showing discolored winding enamel
Thermal image and photo of a dry-type transformer. Temperature scale and equipment labels removed.

What the scan showed: One phase winding of a dry-type transformer was running far hotter than the other two, and its enamel was visibly darkened from heat. It was rated Priority 1. A second transformer in another room showed the same pattern on one phase.

Recommended corrective action: Further testing of both transformers by a licensed electrician, and a review by a qualified electrical engineer.

2. Loose connections at breakers and a disconnect

Infrared image of a three-pole breaker with a hot spot at one connection
Thermal image of a hot connection on a three-pole breaker. Equipment labels removed.

What the scan showed: Several connections ran noticeably hotter than matching parts under the same load: terminals on two three-pole breakers and on a safety switch. That pattern points to high-resistance (loose) connections, which tend to get worse over time.

Recommended corrective action: Clean and tighten the affected connections, and replace parts as needed, by a licensed electrician.

3. A breaker running hotter than its neighbors from unbalanced load

Infrared image of a panelboard with conductors on one three-pole breaker running warm
Photo of the same panelboard and three-pole breaker
Thermal image and photo of a panelboard breaker. Temperature scale and equipment labels removed.

What the scan showed: Conductors on one three-pole breaker were running warmer than the rest of the panel, and the three phases were carrying very different amounts of current: an unbalanced load.

Recommended corrective action: Rebalance the load across the phases and re-scan the panel.

What else the walk-through turned up

Not every problem shows up as heat. While the gear was open, the survey also noted double-tapped conductors, a loose neutral bar, mismatched fuses in a safety switch, heat damage on one phase of a main switchboard, and a transformer installed facing a wall, so not all of its terminations could be seen for a proper scan.

Photo of a switchboard main lug and conductor showing heat damage on one phase
Photo of a panelboard neutral bar and lugs
Heat damage on a switchboard main (left) and a panelboard neutral bar noted as loose (right).

How findings are prioritized

Each finding in the survey report is rated with the delta-T method: how much hotter a part runs than matching parts under similar load, or than the surrounding air. Priority 1 covers the largest differences and calls for corrective action right away. Priority 4 covers small differences that are worth investigating. The criticality of the equipment is weighed along with the temperature.

Every finding comes with a recommended corrective action. If you need the repairs done, GEM Electrical Contracting can quote and perform them as a separate line item.

An infrared survey is one part of an NFPA 70B electrical maintenance program, along with documented inspections, testing and corrective work. It does not certify a facility as compliant on its own. To talk about an infrared survey for your facility, email info@gem-electricalcontracting.com or call (973) 446-6200.

Credentials

  • NJ MBE and NJ SBE certified
  • Prequalified: NJ DPMC · NJ SDA · NJ PWC
  • ISNetworld member, ISN ID 400-559073
  • EMR 0.891 (2026), below the 1.0 industry average
  • OSHA 10 and OSHA 30 trained, scissor lift certified crews
  • NJ Electrical Contractor License #15653
  • Foreman-led crews

Book a 15-minute walk-through.

We’ll look at your gear and tell you where your NFPA 70B program stands. (973) 446-6200

Book a 15-minute walk-through

Frequently asked questions

Is NFPA 70B now a standard?

Yes. NFPA 70B changed from a recommended practice to a standard with the 2023 edition. It calls for a documented electrical maintenance program, and insurers and auditors are starting to ask plants for one.

What does NFPA 70B require for infrared inspections?

NFPA 70B calls for periodic maintenance that includes infrared thermography, with the inspection frequency based on the condition of the equipment. GEM delivers complete NFPA 70B programs: infrared surveys by certified thermographers, arc flash studies stamped by a licensed New Jersey Professional Engineer, and the corrective work, all under one contract and one point of contact. Surveys are performed by Infraspection Institute Certified Infrared Thermographers, following the Infraspection Institute’s Standard for Infrared Inspection of Electrical Systems & Rotating Equipment, and our crews open and prep the gear and correct what the scan finds.

What problems can an electrical infrared survey catch?

Loose terminations, shared neutrals and overfilled conduit can run hot for years until something fails. At one facility, GEM traced a burned-up UPS to two circuits sharing one overloaded neutral and found the main 3/4″ conduit to the ladder tray running extremely hot. Both are the kind of problems an infrared survey is designed to catch.

Can NFPA 70B maintenance be scheduled around production?

Yes. GEM plans night and weekend work around production, and after-hours backup is available if something can’t wait. On a recent plant survey, our crew opened and prepped about 50 pieces of equipment in one morning.

Who installs and updates arc-flash labels in New Jersey?

GEM installs arc-flash labels and updates them after changes to the gear, since every change since the last study makes labels less accurate. The arc flash studies behind the labels are stamped by a licensed New Jersey Professional Engineer, and GEM manages the study, labeling and corrective work under one contract.

How are infrared survey findings prioritized?

Infrared findings are rated with the delta-T method: how much hotter a part runs than matching parts under similar load, or than the surrounding air. Priority 1 covers the largest differences and calls for corrective action right away. Priorities 2 to 4 cover smaller differences, from monitoring until it can be corrected down to worth investigating. Equipment criticality is weighed along with temperature. Every finding comes with a recommended corrective action, and GEM Electrical Contracting can quote and perform the repairs as a separate line item.